Noise level reduction, dB (Octave-frequency band [Hz])
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
SRF 100/600 6 8 13 22 28 34 17 20
SRF 100/900 8 10 15 25 33 40 21 23
SRF 100/2000 10 15 24 48 53 51 39 36
SRF 125/600 4 7 14 20 31 31 13 12
SRF 125/900 5 9 16 23 36 37 17 16
SRF 125/2000 7 15 23 47 55 50 28 25
SRF 150/600 3 7 12 32 40 40 19 20
SRF 150/900 4 8 14 40 48 49 26 25
SRF 150/2000 5 10 21 42 50 48 26 25
SRF 160/600 3 7 12 20 25 24 10 12
SRF 160/900 3 8 13 21 28 28 13 16
SRF 160/2000 5 11 20 40 48 48 25 25
SRF 200/600 2 5 12 20 26 21 10 10
SRF 200/900 3 6 12 22 28 24 12 13
SRF 200/2000 4 11 22 42 51 34 19 23
SRF 250/600 2 3 8 16 22 13 10 10
SRF 250/900 2 4 9 18 25 16 11 12
SRF 250/2000 3 6 16 30 39 27 17 22
SRF 315/600 2 4 9 18 21 12 7 9
SRF 315/900 2 5 11 21 24 14 8 10
SRF 315/2000 4 7 17 34 39 24 14 18